Applications Features
Article Article number Dimensions (W x H x D) [mm] Nominal volume flow [m³ / h] Initial pressure drop [Pa] Filter class acc. to ISO 29463 Filter class acc. to EN 1822 MPPS efficiency [%] 1
SF14-B-0288x0593x292/V06x25-N10N 53417294 288 x 593 x 292 1,800 320 ISO 45 H H14 ≥ 99,995
SF14-B-0305x0305x292/V06x25-N10N 53415772 305 x 305 x 292 1,000 320 ISO 45 H H14 ≥ 99,995
SF14-B-0305x0610x292/V06x25-N10N 53418697 305 x 610 x 292 2,000 320 ISO 45 H H14 ≥ 99,995
SF14-B-0593x0593x292/V12x25-N10N 53429101 593 x 593 x 292 3,600 320 ISO 45 H H14 ≥ 99,995
SF14-B-0610x0610x292/V12x25-N10N 53412194 610 x 610 x 292 4,000 320 ISO 45 H H14 ≥ 99,995
1 Most Penetrating Particle Size efficiency [%]
Filter class H14
Filter class H14
Microbiologically inactive
Microbiologically inactive
Moisture-resistant up to 100% relative humidity
Moisture-resistant up to 100% relative humidity
Easy installation
Easy installation
HEPA Filters High Volume Flow Filters (H14)
High volume flow filters also available without grips.
High volume flow filters also available without grips.

Applications

Viledon high volume flow filters are used in intake, exhaust and recirculated air filtration in cleanrooms in air-conditioning systems with ultra-stringent requirements for clean air quality and sterility, e.g.
  • in sophisticated air-conditioning technology (operating theaters / intensive care units in hospitals and medical institutes, pharmacies, sterile rooms, labs, research centers, etc.)
  • in sensitive industrial processes (pharmaceuticals, biotechnology, chemicals, optics, food and beverage processing, micro-electronics,
    etc.)
HEPA Filters High Volume Flow Filters (H14)
Grips and a gripping lug at the side for easier handling and installation.
Grips and a gripping lug at the side for easier handling and installation.

Features

  • High-efficiency micro-glass-fiber papers are used as filter media.
  • The MiniPleat technology employed, plus the V-shaped configuration of the pleat package, ensure a particularly large filtering area for maximum air flow rate per filter element together with homogeneous media velocity, coupled with a very low pressure drop. This means particularly cost-efficient and dependable operation with a very long lifetime.
  • Viledon high volume flow filters feature recessed grips at the side and a gripping lug for easier handling and installation
  • The frame consists of galvanized steel or stainless steel sheeting and is extremely solid and moisture-resistant.
  • Each filter element is tested for leakproofing in accordance with EN 1822,
    and delivered together with the corresponding test certificate.
  • Viledon high volume flow filters are microbiologically inactive and meet all hygiene requirements of the German VDI Guideline 6022 “Hygiene requirements for HVAC systems and units”.
  • A continuous and homogeneously foamed-on profile gasket made of polyurethane. Also available with a flat gasket on request.