HEPA high volume flow filter Galvanized steel frame H14
HEPA high volume flow filter

Galvanized steel frame H14

Efficient air filtration in cleanrooms

Viledon high volume flow filters are used in intake, exhaust and recirculating air filtration in clean rooms in air-conditioning systems with ultra-stringent requirements for clean air quality and sterility.

Applications Features
Article Datasheet Article number Dimensions (W x H x D) [mm] Filter class acc. to EN 1822 MPPS efficiency [%] 1 Nominal volume flow
[m³/h]
Initial pressure drop [Pa] Face velocity
[m/s]
SF14-B-0288x0593x292/V06x25-N10N-V27-ACA 73117875 288 x 593 x 292 H14 ≥99,995 1,800 380 2.93
SF14-B-0288x0593x292/V06x25-N10N-V27-NTR-ACA 73117897 288 x 593 x 292 H14 ≥99,995 1,800 380 2.93
SF14-B-0305x0305x292/V06x25-N10N-V27-ACA 73117874 305 x 305 x 292 H14 ≥99,995 1,000 380 2.99
SF14-B-0305x0610x292/V06x25-N10N-V27-NTR-ACA 73117903 305 x 610 x 292 H14 ≥99,995 2,000 380 2.99
SF14-B-0305x0610x292/V06x25-N10N-V27-ACA 73117879 305 x 610 x 292 H14 ≥99,995 2,000 380 2.99
SF14-B-0490x0593x292/V10x25-N10N-V27-ACA 73117876 490 x 593 x 292 H14 ≥99,995 2,700 380 2.58
SF14-B-0593x0593x292/V08x25-N10F-V27-ACA 73117890 593 x 593 x 292 H14 ≥99,995 2,400 380 1.90
SF14-B-0593x0593x292/V12x25-N10N-V27-ACA 73116303 593 x 593 x 292 H14 ≥99,995 3,600 380 2.84
SF14-B-0593x0593x292/V12x25-N10N-V27-NTR-ACA 73117900 593 x 593 x 292 H14 ≥99,995 3,600 380 2.84
SF14-B-0610x0610x292/V12x25-N10N-V27-NTR-ACA 73117906 610 x 610 x 292 H14 ≥99,995 4,000 380 2.99
SF14-B-0610x0610x292/V12x25-N10N-V27-ACA 73116223 610 x 610 x 292 H14 ≥99,995 4,000 380 2.99
SF14-B-0610x0762x292/V14x25-N10N-V27-ACA 73117888 610 x 762 x 292 H14 ≥99,995 5,000 380 2.99
1 MPPS: Most Penetrating Particle Size efficiency [%]
<p>Filter class H14</p>

Filter class H14

Microbiologically inactive
Microbiologically inactive
Moisture-resistant up to 100% relative humidity
Moisture-resistant up to 100% relative humidity
Easy installation
Easy installation
HEPA high volume flow filter Galvanized steel frame H14
High volume flow HEPA filters are also available without grip tabs.
High volume flow HEPA filters are also available without grip tabs.

Applications

Viledon high volume flow filters are used in intake, exhaust and recirculated air filtration in cleanrooms in air-conditioning systems with ultra-stringent requirements for clean air quality and sterility, e.g.
  • in sophisticated air-conditioning technology (operating theaters / intensive care units in hospitals and medical institutes, pharmacies, sterile rooms, labs, research centers, etc.)

  • in sensitive industrial processes (pharmaceuticals, biotechnology, chemicals, optics, food and beverage processing, micro-electronics,
    etc.)

HEPA high volume flow filter Galvanized steel frame H14
Side recessed grip and grip tabs for easier handling and assembly.
Side recessed grip and grip tabs for easier handling and assembly.

Features

  • High-efficiency micro-glass-fiber papers are used as filter media.

  • The MiniPleat technology employed, plus the V-shaped configuration of the pleat package, ensure a particularly large filtering area for maximum air flow rate per filter element together with homogeneous media velocity, coupled with a very low pressure drop. This means particularly cost-efficient and dependable operation with a very long lifetime.

  • Viledon high volume flow filters feature recessed grips at the side and a gripping lug for easier handling and installation

  • The frame consists of galvanized steel and is extremely solid and moisture-resistant.

  • Each filter element is tested for leakproofing in accordance with EN 1822,
    and delivered together with the corresponding test certificate.

  • Viledon high volume flow filters are microbiologically inactive and meet all hygiene requirements of the German VDI Guideline 6022 “Hygiene requirements for HVAC systems and units”.

  • A continuous and homogeneously foamed-on profile gasket made of polyurethane. Also available with a flat gasket on request.