HEPA high volume flow filter Galvanized steel frame H13
HEPA high volume flow filter

Galvanized steel frame H13

Efficient air filtration in cleanrooms

Viledon high volume flow filters are used in intake, exhaust and recirculating air filtration in clean rooms in air-conditioning systems with ultra-stringent requirements for clean air quality and sterility.

Applications Features
Article Datasheet Article number Dimensions (W x H x D) [mm] Filter class acc. to EN 1822 MPPS efficiency [%] 1 Nominal volume flow
[m³/h]
Initial pressure drop [Pa] Face velocity
[m/s]
SF13-B-0288X0288X292/V06X25-N10N-XXX 53438538 288 x 288 x 292 H13 ≥99,95 1,000 250 3.35
SF13-B-0288X0593X292/V06X25-N10N-J27-NTR 73043192 288 x 593 x 292 H13 ≥99,95 1,800 250 2.93
SF13-B-0288X0593X292/V06X25-N10N-XXX 53412638 288 x 593 x 292 H13 ≥99,95 1,800 250 2.93
SF13-B-0288X0593X292/V08X25-N10F-J27 53470176 288 x 593 x 292 H13 ≥99,95 1,300 250 2.11
SF13-B-0305X0305X292/V06X25-N10N-J27-NTR 73043201 305 x 305 x 292 H13 ≥99,95 1,000 250 2.99
SF13-B-0305X0305X292/V06X25-N10N-XXX 53411980 305 x 305 x 292 H13 ≥99,95 1,000 250 2.99
SF13-B-0305X0610X292/V06X25-N10N-J27-NTR 73043206 305 x 610 x 292 H13 ≥99,95 2,000 250 2.99
SF13-B-0305X0610X292/V06X25-N10N-XXX 53412052 305 x 610 x 292 H13 ≥99,95 2,000 250 2.99
SF13-B-0457X0457X292/V08X25-N10N-XXX 53421083 457 x 457 x 292 H13 ≥99,95 1,800 250 2.39
SF13-B-0457X0610X292/V08X25-N10N-J27 53533612 457 x 610 x 292 H13 ≥99,95 800 75 0.80
SF13-B-0490X0593X292/V08X25-N10F-U27 53530546 490 x 593 x 292 H13 ≥99,95 1,900 250 1.82
SF13-B-0490X0593X292/V10X25-N10N-J27 53533613 490 x 593 x 292 H13 ≥99,95 3,000 250 2.87
SF13-B-0490X0593X292/V10X25-N10N-J27-NTR 73043194 490 x 593 x 292 H13 ≥99,95 3,000 250 2.87
SF13-B-0494X0494X292/V08X25-N11N-J27 53448861 494 x 494 x 292 H13 ≥99,95 2,500 250 2.85
SF13-B-0593X0593X292/V08X25-N10F-J27 53470177 593 x 593 x 292 H13 ≥99,95 3,000 250 2.37
SF13-B-0593X0593X292/V12X25-N10N-J27-NTR 73043198 593 x 593 x 292 H13 ≥99,95 3,600 250 2.84
SF13-B-0593X0593X292/V12X25-N10N-XXX 53412644 593 x 593 x 292 H13 ≥99,95 3,600 250 2.84
SF13-B-0610X0610X292/V10X25-N10N-J27-NTR 73043125 610 x 610 x 292 H13 ≥99,95 3,400 250 2.54
SF13-B-0610X0610X292/V10X25-N10N-XXX 53412060 610 x 610 x 292 H13 ≥99,95 3,400 250 2.54
SF13-B-0610X0610X292/V12X25-N10N-J27-NTR 73043218 610 x 610 x 292 H13 ≥99,95 4,000 250 2.99
SF13-B-0610X0610X292/V12X25-N10N-OS-J27 53616141 610 x 610 x 292 H13 ≥99,95 4,000 250 2.99
SF13-B-0610X0610X292/V12X25-N10N-XXX 53412054 610 x 610 x 292 H13 ≥99,95 4,000 250 2.99
SF13-B-0610X0610X292/V12X25-W10N-XXX 53412059 610 x 610 x 292 H13 ≥99,95 4,000 250 2.99
SF13-B-0610X0762X292/V14X25-N10N-J27-NTR 73043229 610 x 762 x 292 H13 ≥99,95 5,000 250 2.99
SF13-B-0610X0762X292/V14X25-N10N-XXX 53412056 610 x 762 x 292 H13 ≥99,95 5,000 250 2.99
SF13-B-0610X0762X292/V14X25-N11N-J27-NTR 73043238 610 x 762 x 292 H13 ≥99,95 5,000 250 2.99
1 MPPS: Most Penetrating Particle Size efficiency [%]
Filter class H13
Filter class H13
Microbiologically inactive
Microbiologically inactive
Moisture-resistant up to 100% relative humidity
Moisture-resistant up to 100% relative humidity
Easy installation
Easy installation
HEPA high volume flow filter Galvanized steel frame H13
High volume flow HEPA filters are also available without grip tabs.
High volume flow HEPA filters are also available without grip tabs.

Applications

Viledon high volume flow filters are used in intake, exhaust and recirculated air filtration in cleanrooms in air-conditioning systems with ultra-stringent requirements for clean air quality and sterility, e.g.
  • in sophisticated air-conditioning technology (operating theaters / intensive care units in hospitals and medical institutes, pharmacies, sterile rooms, labs, research centers, etc.)

  • in sensitive industrial processes (pharmaceuticals, biotechnology, chemicals, optics, food and beverage processing, micro-electronics,
    etc.)

HEPA high volume flow filter Galvanized steel frame H13
Side recessed grip and grip tabs for easier handling and assembly.
Side recessed grip and grip tabs for easier handling and assembly.

Features

  • High-efficiency micro-glass-fiber papers are used as filter media.

  • The MiniPleat technology employed, plus the V-shaped configuration of the pleat package, ensure a particularly large filtering area for maximum air flow rate per filter element together with homogeneous media velocity, coupled with a very low pressure drop. This means particularly cost-efficient and dependable operation with a very long lifetime.

  • Viledon high volume flow filters feature recessed grips at the side and a gripping lug for easier handling and installation

  • The frame consists of galvanized steel and is extremely solid and moisture-resistant. Variants with stainless steel frame are also available.

  • Each filter element is tested for leakproofing in accordance with EN 1822,
    and delivered together with the corresponding test certificate.

  • Viledon high volume flow filters are microbiologically inactive and meet all hygiene requirements of the German VDI Guideline 6022 “Hygiene requirements for HVAC systems and units”.

  • A continuous and homogeneously foamed-on profile gasket made of polyurethane. Also available with a flat gasket on request.