ULPA filter with PU gasket Aluminum frame U15
ULPA filter with PU gasket

Aluminum frame U15

Efficient air filtration in cleanrooms

Viledon ULPA filters with aluminum frame and PU gasket of filter classes U15 guarantee effective protection for sensitive products and processes by reliable arrestance of critical particles.


Applications Features
Article Datasheet Article number Dimensions (W x H x D) [mm] Filter class acc. to EN 1822 MPPS efficiency [%] 1 Nominal volume flow
[m³/h]
Initial pressure drop [Pa] Face velocity
[m/s]
SF15-A-0305X0305X068X05-N13N-XXX 53429059 305 x 305 x 68 U15 ≥99,9995 120 150 0.36
SF15-A-0305X0610X066X05-N13N-V39 53471474 305 x 610 x 66 U15 ≥99,9995 280 150 0.42
SF15-A-0457X0457X068X05-N13N-V39-NTR 73043038 457 x 457 x 68 U15 ≥99,9995 450 150 0.60
SF15-A-0457X0610X068X05-N13N-V39 53573360 457 x 610 x 68 U15 ≥99,9995 450 150 0.45
SF15-A-0457X0915X068X05-N13N-V39 53470437 457 x 915 x 68 U15 ≥99,9995 670 150 0.45
SF15-A-0610X0610X066X05-N13N-V39 53471475 610 x 610 x 66 U15 ≥99,9995 600 150 0.45
SF15-A-0610X0610X068X05-N13N-V39 610 x 610 x 68 U15 ≥99,9995 600 150 0.45
SF15-A-0610X0610X068X05-N13N-V39-NTR 73043057 610 x 610 x 68 U15 ≥99,9995 600 150 0.45
SF15-A-0610X0610X078X06-N13N-V39 610 x 610 x 78 U15 ≥99,9995 600 125 0.45
SF15-A-0610X0610X088X07-N13N-V39 53472104 610 x 610 x 88 U15 ≥99,9995 600 115 0.45
SF15-A-0610X0915X066X05-N13N-V39 53471476 610 x 915 x 66 U15 ≥99,9995 900 150 0.45
SF15-A-0610X0915X068X05-N13N-V39 53445047 610 x 915 x 68 U15 ≥99,9995 900 150 0.45
SF15-A-0610X0915X068X05-N13N-V39-NTR 73043066 610 x 915 x 68 U15 ≥99,9995 900 150 0.45
SF15-A-0610X0915X088X07-N13N-XXX 53424196 610 x 915 x 88 U15 ≥99,9995 900 115 0.45
SF15-A-0610X1220X068X05-N13N-XXX 53427808 610 x 1220 x 68 U15 ≥99,9995 1,200 150 0.45
SF15-A-0610X1220X088X07-N13N-XXX 53431655 610 x 1220 x 88 U15 ≥99,9995 1,200 115 0.45
SF15-A-0610X1830X068X05-N13N-V39 53507883 610 x 1830 x 68 U15 ≥99,9995 1,800 150 0.45
SF15-A-0762X0915X066X05-N13N-V39 53471477 762 x 915 x 66 U15 ≥99,9995 1,125 150 0.45
SF15-A-0762X1525X066X05-N13N-V39 53471478 762 x 1525 x 66 U15 ≥99,9995 1,875 150 0.45
SF15-A-0762X1525X068X05-N13N-V39 53445049 762 x 1525 x 68 U15 ≥99,9995 1,875 150 0.45
SF15-A-0915X0915X068X05-N13N-V39 53490686 915 x 915 x 68 U15 ≥99,9995 1,350 150 0.45
1 MPPS: Most Penetrating Particle Size efficiency [%]
Filter class U15
Filter class U15
Moisture-resistant up to 100% relative humidity
Moisture-resistant up to 100% relative humidity
Microbiologically inactive
Microbiologically inactive
Optimized cost-efficiency
Optimized cost-efficiency
High functional dependability
High functional dependability
ULPA filter with PU gasket Aluminum frame U15
Protection grids on both sides made of powdercoated expanded metal.
Protection grids on both sides made of powdercoated expanded metal.

Applications

Viledon ULPA filters with aluminum frame are used in intake and recirculated air filtration for cleanrooms and in laminar flow boxes with ultra-stringent requirements for clean air and sterility, e. g.
  • in sophisticated air-conditioning applications (operating theatres/intensive care units of hospitals and medical institutes, pharmacies, sterile rooms, labs, research centers, etc.)

  • in sensitive industrial processes (pharmaceuticals, biotechnology, chemicals, optics, food/beverages, micro-electronics, etc.)

  • in ceiling outlets and modules for flexible cleanroom systems.

ULPA filter with PU gasket Aluminum frame U15
The MiniPleat technology ensures homogeneous media velocity coupled with a very low pressure drop.
The MiniPleat technology ensures homogeneous media velocity coupled with a very low pressure drop.

Features

  • High-efficiency micro-glass-fiber papers are used as filter media.

  • The MiniPleat technology employed ensures flow-friendly geometry and equidistance of the pleats, with homogeneous media velocity coupled with a very low pressure drop. This means particularly cost-efficient and dependable operation plus a quasilaminar outflow.

  • The frame consists of extruded, anodized aluminum and is extremely solid and moisture-resistant.

  • Viledon ULPA filters are microbiologically inactive and meet all hygiene requirements of the German VDI Guideline 6022 “Hygiene requirements for HVAC systems and units”.

  • Each filter element is tested using state-of-the-art scanning equipment for arrestance efficiency and leakproofing in accordance with EN 1822, and delivered together with the corresponding test certificate.